0 like search mail home
選擇品牌 arrow_down

CMP-2000

Digital clamp-on multimeter 型號:CMP-2000
Universal clamp meter, enabling the maintenance of current measurements up to 2000 A, with the diameter of the clamp as 57 mm, and bus bar to 70 * 18 mm
The instrument has an electronic overload protection of all functions and ranges.
  • It provides:
    • AC current measurement (TRUE RMS) up to 1500 A and DC up to 2000 A.
    • Measurement of INRUSH current in start-up phase of electrical device.
    • AC voltage measurement (TRUE RMS) up to 750 V and DC up to 1000 V.
    • Resistance measurement and continuity test:
      - continuity test with acoustic signalling (beeper) for resistance below 30 Ω.
    • Capacitance measurement.
    • Temperature measurement (Fahrenheit or Celsius).
    • Frequency measurement.
    • Duty cycle measurement.
    • Diode test.

    Special features:

    • safe, insulated measuring clamp,
    • autoranging,
    • „DATA HOLD” function, for holding measured values,
    • backlit LCD,
    • „DC ZERO” mode of measurement for DC current, possibility to zero the display and reading relative actual value less stored „zero” value,
    • „MAX/MIN” function,
    • over range indication,
    • „AUTO-OFF” function after 30 min.
  • Electric security:

    • measurement category: CAT IV 600 V acc. to EN 61010 - 1,
    • protection class acc. to EN 60529: IP20,

    Other technical data:

    • power supply, 9 V battery type 6LR61,
    • display: 6600 counts, backlit LCD,
    • continuity test: threshold 30 Ω,
    • diode test: test current of 0,8 mA , typical open circuit voltage 3,2 V DC, typical,
    • low battery indication: BAT displayed,
    • over range indication: ‘OL’ displayed,
    • temperature sensor: type K thermocouple,
    • input impedance: ca.10 MΩ (V DC and V AC),
    • AC bandwidth: 50...500 Hz,
    • auto power OFF: 30 minutes,
    • dimensions: 281 x 108 x 53 mm,
    • weight: 570 g (with battery),
    • accordance with following standards: EN 61010 - 1, EN 61010 - 2-032.

    Rated operational conditions:

    • able to open the clamp: Ø 57 mm wire 70 x 18 mm bus bar,
    • operating temperature: 0...+50 °C,
    • storage temperature: -20...+60 °C,
    • operating altitude: max 2000 m.

    DC current measurement

    Range Resolution Accuracy
    0,0...659,9 A 0,1 A ±(2,0% m.v. + 5 digits)
    660...2000 A 1 A ±(3,0% m.v. + 5 digits) for 660...1000 A
    ±(5,0% m.v. + 5 digits) for 1000...2000 A

    AC current measurement (TRUE RMS)

    Range Resolution Accuracy
    0,0...659,9 A 0,1 A ±(2,0% m.v. + 10 digits) for 50...60 Hz
    ±(3,0% m.v. + 10 digits) for 61...400 Hz
    660...1500 A 1 A ±(2,5% m.v. + 10 digits) for 50...60 Hz
    i 660...1000 A
    ±(3,5% m.v. + 10 digits) for 61...400 Hz
    and 660...1000 A
    ±(5,0% m.v. + 10 digits) for 50...400 Hz
    and 1000...1500

    DC voltage measurement

    Range Resolution Accuracy
    0,000...6,599 V 0,001 V ±(0,5% m.v. + 2 digits)
    6,60...65,99 V 0,01 V
    66,0...659,9 V 0,1 V
    660...1000 V 1 V

    AC voltage measurement (true RMS)

    Range Resolution Accuracy
    0,000...6,599 V 0,001 V ±(1,5% m.v. + 8 digits)
    for 50...500 Hz
    6,60...65,99 V 0,01 V
    66,0...659,9 V 0,1 V
    660...750 V 1

    Resistance measurement

    Range Resolution Accuracy
    0,0...659,9 Ω 0,1 Ω ±(1,0% m.v. + 5 digits)
    0,660...6,599 kΩ 0,001 kΩ
    6,60...65,99 kΩ 0,01 kΩ
    66,0...659,9 kΩ 0,1 kΩ
    0,660...6,599 MΩ 0,001 MΩ ±(2,0% m.v. + 5 digits)
    6,60...66,00 MΩ 0,01 MΩ ±(3,5% m.v. + 5 digits)

    Capacitance measurement

    Range Resolution Accuracy
    0,0...6,599 nF 0,001 nF ±(3,0% m.v. + 30 digits)
    6,60...65,99 nF 0,01 nF ±(3,0% m.v. + 10 digits)
    66,0...559,9 nF 0,1 nF ±(3,0% m.v. + 30 digits)
    6,600...59,999 µF 0,001 µF ±(3,0% m.v. + 10 digits)
    66,00...659,99 µF 0,01 µF
    660...659,999 µF 0,100 µF
    0,660...6,600 mF 0,001 mF

    Frequency measurement

    Range Resolution Accuracy
    10...65,99 Hz 0,01 Hz ±(0,1% m.v. + 5 digits)
    66,0...659,9 Hz 0,1 Hz
    0,660...6,599 kHz 0,001 kHz
    6,60...65,99 kHz 0,01 kHz
    66,0...659,9 kHz 0,1 kHz
    0,660...1,000 MHz 0,001 MHz

    Temperature measurement

    Range Resolution Accuracy
    -20...0°C 1°C ±(2,0% m.v. + 3°C)
    0...399°C ±(1,0% m.v. + 2°C)
    400...1000°C ±(2,0% m.v. + 3°C)
    -4...31°F 1°F ±(2,0% m.v. + 6°F)
    32..749°F ±(1,0% m.v. + 4°F)
    750...1832°F ±(2,0% m.v. + 6°F)

    Duty cycle measurement

    ange Resolution Accuracy
    5...95% 0,1% ±(2,0% m.v. + 10 digits)

    „m.v.”- measured value